Vallox’s new automatic control system – demand-controlled ventilation and real energy savings
Published 01.09.2026
Modified 23.11.2026
Writer: Marko Kannisto, Product Manager
Summary
The general view is that a flat should have a constant ventilation rate of 0.5, even though the regulations only require adequate and effective ventilation — not a specific figure. When a ventilation unit is fitted with reliable humidity and carbon dioxide sensors, the ventilation can be sized and controlled according to actual demand, rather than being maintained constantly at the level required for the occupied space as a precaution. This article examines how ventilation requirements and their design limits are determined, which indoor air quality indicators are effective in practice, and how much energy and cost can be saved with demand-controlled, sensor-controlled ventilation (Vallox Automatic Control) can save, compared with continuous ventilation of occupied spaces. This article is intended for designers and other experts who assess the sizing and control methods of ventilation systems from the perspective of energy efficiency.
1. Framing the problem
Many people believe that a flat should have a constant ventilation rate of 0.5. In reality, the regulations refer to adequate and effective ventilation, not to a specific figure. When there is no excess moisture or carbon dioxide in the flat, a ventilation rate of 0.5 times the actual requirement may be higher than is actually necessary.
It is worth noting that, although modern ventilation units have a high annual efficiency, any excess ventilation is nonetheless — particularly in winter — a waste of energy. Even the indoor temperature is not usually raised by more than a couple or three degrees simply as a precaution, so by the same token one might ask why ventilation should be set any higher than is actually necessary.
Ventilation design for different operating conditions
The ventilation plan usually specifies the airflows for the ‘in use’, ‘absent’ and ‘boost’ modes. For example, the guide published by FINVAC ry, ‘Guide to the Design of Ventilation in Residential Buildings’, lists the airflows in different rooms of a flat during normal use — this corresponds to the airflow in the occupied space (or ‘at home’ space). The guide also states that it must be possible to increase the ventilation rate to 30 per cent above the normal operating rate, and that it must be possible to reduce the ventilation rate to 60 per cent of the normal operating rate.
The guide also states that a lower ventilation setting may only be used when the flat is unoccupied and there are no specific sources of humidity or pollutants (a bathroom drying out, washing drying, pets, and so on).
However, the situation is different if the ventilation unit is fitted with, for example, humidity and carbon dioxide sensors: in which case it is reasonable to ask why the ventilation rate should be any higher than is actually necessary — regardless of whether a resident or a pet is present or not.
Practical indicators of indoor air quality
Although the research literature identifies numerous different indicators for assessing indoor air quality, only a few of them are genuinely suitable for practical residential use and ongoing monitoring. According to Eurovent, there are, in theory, dozens of indicators for monitoring indoor air quality, but in practice, the only ones worth using are those that are technically reliable, cost-effective and can be measured continuously.
The most important of these are relative humidity and carbon dioxide concentration. Relative humidity provides a direct indication of the moisture conditions within a building and its occupied spaces, whilst carbon dioxide levels serve as a reliable indicator of the adequacy of ventilation and the level of human activity. As long as these two factors are kept under control, the ventilation system will meet actual requirements without having to be oversized as a precaution — and this is precisely the basis of genuinely needs-based ventilation.
2. Method / principle
How automatic steering works
MyVallox ventilation units have both humidity and carbon dioxide sensors built in, so the unit continuously measures two key parameters relating to indoor air quality.
Vallox Automatic Control is a control mode that does not require any separate settings to be made by the user or the installer. It utilises the existing airflow and temperature settings for ‘at home’ and ‘away’ modes. In automatic control mode, humidity and carbon dioxide control are always active and cannot be switched off, which ensures that the ventilation system always responds to actual demand.
The operating principle is simple: the ventilation unit adjusts the ventilation as required and prevents unnecessary over-ventilation. Provided there is no excess moisture or carbon dioxide in the flat, the unit will not over-ventilate it; instead, the ventilation level will remain in line with actual requirements.
Principles for calculating energy consumption
When comparing the energy consumption of ventilation systems, it is important to take into account not only the heat recovery provided by the ventilation unit, but also the contribution made by the dwelling’s primary heating system (the dwelling’s actual heating system). This is because when energy consumption is calculated using an exhaust air temperature of 21 °C and a supply air temperature of 17 °C — as is usually the case — there is a 4-degree temperature difference between the indoor air and the supply air. This missing thermal energy comes from the flat’s primary heating system. So, in terms of energy consumption, it is not free.
The key variables in the calculation and the relationships between them are:
- Energy consumption for ventilation = Annual energy requirement for ventilation − energy recovered through heat recovery.
- Energy requirement of the primary heating system = the amount of energy required to heat the supply air, after heat recovery, to the indoor air temperature.
- Total energy consumption = Energy consumption for ventilation + Energy requirement of the primary heating system.
3. Application example
The example given is the MyVallox 149 CFi unit, which has an annual efficiency of 83 per cent. The calculation is based on an air flow rate of 65 l/s in the occupied space, climate zone I (Southern Finland, Helsinki-Vantaa) and the TRY2020 climate data set. Energy consumption is calculated on the basis of an exhaust air temperature of 21 °C and a supply air temperature of 17 °C, and the additional energy required by the flat’s primary heating system has also been included in the calculation.
In the first operating scenario, the ventilation unit remains in ‘home’ mode at all times (100 per cent of the time, with an operating airflow of 65 l/s). In another scenario, the actual ventilation requirement is 65 l/s for half the time and 40 l/s for the other half (for example, when the flat is unoccupied 50 per cent of the time).
- Difference in total energy consumption: 486 kWh/a.
- Assumed electricity price: 0.2 €/kWh.
- Cost impact: approximately €97 per year.
In any given year, a cost difference of €97 is not significant, but it is a cost that is, in principle, entirely avoidable. When calculated over a ten-year period, the cumulative total becomes significantly larger.
4. Design recommendation
- Size the ventilation system according to actual requirements. When reliable humidity and carbon dioxide sensors are in use, ventilation does not need to be maintained at a constant rate of 0.5 times the occupancy level or at the occupancy level itself; instead, it can be controlled according to the actual occupancy within the limits permitted by FINVAC.
- Opt for sensor-based automatic control rather than a fixed time programme. A timer or weekly timer does not respond to actual, fluctuating loads. An air-flow-controlled automatic control system (e.g. Vallox Automatic Control) continuously adjusts the ventilation without the user needing to know how to adjust the system themselves.
- Select the variables to be monitored from among the indicators that work in practice. Relative humidity and carbon dioxide concentration are technically reliable, cost-effective and can be measured continuously, unlike many theoretical indoor air quality indicators.
- When carrying out energy calculations, please also take into account the contribution of the primary heating system. Simply looking at the heat recovery in the ventilation unit underestimates the actual energy consumption and, consequently, the potential for savings through demand-based control.
Pitfalls:
- A high annual efficiency does not eliminate the drawbacks of over-ventilation: an oversized ventilation system that continuously operates at the air flow rate of the occupied space consumes unnecessary energy, even if the unit itself is efficient.
- Reduced ventilation without humidity control is only suitable for situations where there are no specific sources of humidity or pollutants — for example, when a flat is unoccupied.
- Not all indoor air quality parameters that are theoretically possible are suitable for continuous monitoring in practice; it is advisable to choose parameters that are reliable, cost-effective and can be measured continuously.
Sensor-based automatic control enables ventilation to be adjusted as required, without the user having to constantly adjust the system or be an expert in ventilation.
5. References and related documents
FINVAC ry. ”Opas asuinrakennusten ilmanvaihdon mitoitukseen.” or english article about it.
Eurovent.eu — Guidance on indoor air quality indicators
MyVallox 149 CFi product documentation and a description of the Vallox Automatic Control function.