Frequently asked questions

On this page, we have compiled the most frequently asked questions and answers related to ventilation and Vallox products. These frequently asked questions help you to quickly find answers to topics such as the operation, settings, commissioning, and troubleshooting of ventilation units. We update the FAQ page regularly so that you can find up-to-date information in one place.

Frequently asked guestions about Vallox ventilation units

Purchasing a MyVallox ventilation unit

What should be considered when choosing the right ventilation unit model?

  1. Airflow capacity: Choose a ventilation unit with airflow rates that match the size of your home and its ventilation requirements. 
  2. Energy efficiency: Select a ventilation unit with a high heat recovery efficiency. 
  3. Versatile control options: Make sure the ventilation unit can be controlled in the way that suits you best, such as with a wall-mounted control panel, a kitchen cooker hood, remotely via your mobile device, or integrated into a home automation system. 
  4. Automation: Ensure that the unit includes advanced defrosting automation and built-in indoor air quality sensors. 
  5. Noise level: Choose a ventilation unit that operates as quietly as possible, especially if it will be installed in the kitchen, bathroom, utility room, or walk-in closet. 
  6. Filter availability: Make sure that compatible replacement filters are readily available. Original manufacturer filters are generally the best option. 
  7. Serviceability and durability: Consider how easy the unit is to maintain and clean, so that its performance and cleanliness can be preserved over the long term. 

All Vallox ventilation units meet the above requirements and features. 

How do I know which Vallox 125 CFi model is suitable to replace my old unit?

The different Vallox 125 CFi models have duct outlet configurations that match many older ventilation unit models, or they require only minor ductwork modifications. The letter in the unit name (A-H) indicates the model type, meaning the arrangement and location of the duct outlets.

In addition, you must verify the unit’s handedness (left-hand or right-hand version), which determines the orientation of the duct outlets in the top section of the unit.

The appropriate replacement model for an existing unit can be checked using the compatibility table (PDF).

For example, the 125A model has the same duct outlet layout as the MUH Ilmava 100, MUH Ilmava 120, and Vallox 121 SE/MC units. These models can therefore be replaced directly with a Vallox 125 CFi unit without any ductwork modifications.

How does the constant airflow feature work?

A standard ventilation unit adjusts the fan speed but cannot compensate for airflow changes caused by factors such as a window being left open temporarily or reduced airflow due to dirty filters.

A MyVallox ventilation unit equipped with the constant airflow feature maintains balanced airflow under all conditions by compensating for pressure differences caused by external factors.

For example, when a filter becomes dirty, the unit automatically increases airflow in the direction of the clogged filter to compensate for the increased resistance, thereby maintaining balanced supply and exhaust air volumes.

What do the abbreviations CFi, MV, MC, SE, K, VKL, R, and L mean?

The abbreviations CFi, MV, MC, and SE that appear after the product name of a Vallox ventilation unit refer to the unit’s control system or operating method.

  • CFi: The letters CF stand for Constant Flow, meaning the unit maintains constant airflow. The “i” stands for Intelligent, referring to the smart total-airflow control that makes commissioning and setup easier than before.
  • MV, MC, and SE: These abbreviations indicate the unit’s control system:
    • MV = MyVallox Control
    • MC = Simple Control
    • SE = Controlled with a Vallox Digit SED controller
  • K: Indicates a ventilation unit with an integrated cooker hood.
  • VKL: Refers to a model equipped with a water-based post-heating coil.
  • R and L: These letters indicate the unit’s handedness (orientation).
    • R (Right-hand model): Outdoor air enters the unit from the right side of the center line.
    • L (Left-hand model): Outdoor air enters the unit from the left side of the center line.

The locations of the other duct connections are correspondingly mirrored from one side to the other.

What is the difference between AC and EC fans?

An AC fan (alternating current fan) operates using traditional alternating current (AC), and its control is typically based on voltage or frequency adjustment. AC fans have been widely used for many years, but their energy efficiency and control capabilities are relatively limited.

An EC fan (electronically commutated fan) is a modern direct current (DC) fan with built-in electronic controls. EC fans are more energy-efficient, quieter, and allow precise speed control, for example through percentage-based adjustment via Vallox control systems. EC fans also enable more accurate balancing of supply and exhaust airflow rates while reducing electricity consumption.

Vallox MV and MyVallox CFi ventilation units use EC fans because they meet modern energy-efficiency requirements and provide versatile control options.

What additional sensors can be used with MyVallox ventilation units?

MyVallox ventilation units always come with built-in humidity and carbon dioxide (CO₂) sensors.

As optional accessories, they can also be connected to room-mounted humidity, CO₂, and VOC sensors.

  • Humidity sensors monitor indoor moisture levels and help the unit adjust ventilation automatically.
  • CO₂ sensors measure carbon dioxide levels, enabling demand-based ventilation according to occupancy.
  • VOC sensors detect volatile organic compounds and other indoor air pollutants, allowing the ventilation system to respond to changes in air quality.

How can Vallox MyVallox ventilation units be connected to a Modbus network?

Vallox MyVallox ventilation units can be connected directly to a Modbus network without the need for a separate adapter. Modbus functionality is built into MyVallox ventilation units as a standard feature.

The Modbus register documentation can be found here.

How can MyVallox ventilation units be connected to a KNX smart home system?

MyVallox MV ventilation units can be connected to a KNX smart home system using a KNX bus converter, which is available as an optional accessory.

The KNX bus converter enables communication between the MyVallox ventilation unit and the KNX automation system, allowing ventilation functions to be monitored and controlled through the KNX network.

Can MyVallox ventilation units be equipped with a cooling or preheating coil connected to a ground-source heat pump system?

A coil connected to the ground-source heat pump collector loop is not available as a built-in option in Vallox ventilation units. However, a MLV duct radiator can be connected to the ventilation system.

The MyVallox unit’s automation system can provide control signals for the pump and solenoid valve of the cooling or preheating circuit. This allows the MLV duct radiator to be used for:

  • Preheating incoming outdoor air during cold weather
  • Cooling supply air during warmer periods

How do you connect a MyVallox ventilation unit to the internet?

The ventilation unit is equipped with a LAN cable, which is connected directly to the router. The ventilation unit does not have a built-in wireless Wi-Fi connection.

If it is not possible to connect the ventilation unit to the router using a cable, a Wi-Fi repeater (Wi-Fi extender) can be installed near the unit. In that case, the ventilation unit’s LAN cable is connected to the Wi-Fi repeater, which is connected wirelessly to the home’s Wi-Fi network.

How can a MyVallox unit be controlled remotely?

MyVallox units, meaning MV and CFi models, can be registered to the browser-based MyVallox Cloud service using an internet connection. Through this service, the units can be controlled over the internet using a computer, tablet, or smartphone. Registration to the service is free of charge.

With a remote connection, all the same functions can be controlled as with the local control panel. Instructions for registering the unit can be found in the device manual and in Vallox WebHelp 

If desired, the unit can also be controlled by connecting it to a building automation system or by connecting it to the home network, allowing it to be controlled through the MyVallox Home service using a device connected to the same home network.

Vallox does not provide a separate application for controlling the ventilation unit.

Can MyVallox ventilation units compensate for the negative pressure caused by a cooker hood or central vacuum system?

Partly, yes.

The exhaust airflow of a cooker hood or central vacuum system can be greater than the total ventilation airflow of the entire dwelling, so it may not always be possible to fully compensate for it with a ventilation unit, unless the unit is equipped with the constant airflow feature. With a CFi unit, negative pressure should not occur.

Compensation with MyVallox MV-units requires a contact output (switching contacts) from the cooker hood, central vacuum cleaner or a pressure difference switch connected to them. The control voltage received from the MV unit is brought through these contacts back to the digital input. At the controller of the MyVallox unit, choose Self-programmed input as the setting for this digital input. After that, choose the desired power for the supply and extract fans in the self-programmed input settings.

What types of controllers can I get for my MyVallox ventilation unit?

MyVallox CFi and MV ventilation units can be controlled with the MyVallox Control controller supplied with the unit, which is based on separate modes, such as Home and Automatic mode, selected by the user. The unit can also be controlled with the newer MyVallox Touch controller, either in parallel or on its own. The Touch controller includes Home, Away, Automatic, Boost and Custom modes, and it can be recessed into the cover plate of certain switch systems. CFi and MV models can also be controlled with a cooker hood and can be connected to a building automation system for remote control, for example via a smartphone (KNX, Modbus, voltage signal). The units can also be connected to the free browser-based MyVallox Cloud service. Of these different control options available for the units, the option best suited to the property and lifestyle can be selected.

MC model ventilation units can be controlled with the separately sold four-speed, easy-to-use Simple Control controller, the Vallox ProControl controller, or a cooker hood. The Vallox ProControl controller has three mode selections (Home, Away and Boost). MC models can also be controlled via a 0-10 V voltage signal. MC models equipped with a ProControl controller can be connected to a Modbus network.

SE refers to a ventilation unit that can be controlled with the Vallox Digit SED controller supplied with the unit. The controller features eight-step speed control. Humidity and carbon dioxide sensors are available as optional accessories for SE models.

Why should I replace my ventilation unit?

It is worth replacing your ventilation unit because the heat recovery core in older ventilation units is often significantly smaller than that of today’s energy-efficient devices. In addition, the fans in new units often consume less electricity than those in older units. If you would like to examine the matter more closely, download the Excel file that allows you to estimate energy consumption based on the price of your own electricity contract and your own ventilation settings.

Can a ventilation unit be controlled with an app?

Vallox does not offer app-based control for its ventilation units.

MyVallox MV and CFi units can be connected to the internet and registered to MyVallox Cloud, a browser-based service that allows the unit to be controlled remotely. The units can also be connected to the MyVallox Home service via an Ethernet connection.

Older models cannot be connected to the MyVallox Cloud service.

Using and Configuring a MyVallox Ventilation Unit

How can heat recovery (HRV) be enabled during airflow adjustment in MyVallox models?

Airflows should always be adjusted with the heat recovery (HRV) function enabled, because the correct supply/exhaust air ratio is particularly important during winter conditions. When a Vallox MyVallox unit is commissioned correctly, heat recovery is active.

Commissioning should be carried out after setting the language, time, and other basic settings by selecting the “Airflow Adjustment” function through either the “Special Settings” menu or the “Settings Backup and Restore” menu.

This puts the unit into Commissioning Mode, where heat recovery is always enabled and the settings made are stored as the commissioning settings.

What is the difference between setup settings and user settings in an MV unit?

The fan, temperature and other settings made during setup are automatically saved as setup settings. Changes made later are automatically saved as user settings. Also changes made later on can be manually saved as setup settings. You can restore both setup and user settings at the controller or via remote control.

Note! When the setup settings are restored, they also overwrite the user settings. Factory settings reset erases both the setup and the user settings from the memory of the unit.

Where can I find instructions of MyVallox ventilation units?

Product-specific operating instructions, maintenance instructions, installation instructions, technical data and dimensions can be found for each MyVallox ventilation unit on the product page.

Also, you can use WebHelp that contains instructions for the setup, use and maintenance of your MyVallox ventilation unit. WebHelp is available online and is easy to use either on a computer or a mobile phone.

Can I modify the ventilation unit settings myself as a user?

The factory settings of Vallox ventilation units have been selected to ensure that the unit operates as energy-efficiently as possible. Do not change any settings unless you know what you are changing and how it will affect the operation of the unit. If you change any setting, make a note of both the original value and the new value so that you can restore it if necessary. The unit operates correctly and economically with the factory settings.

If you wish to modify the settings, you can adjust the supply air temperature, defrost settings, heating settings, control settings, external sensor settings, and cooker hood compensation settings from the Professional Settings section in the unit’s menu. More detailed instructions can be found in the unit’s user manual.

What does post-heating mean?

MyVallox CFi and MV ventilation units are equipped with an electric post-heating element inside the unit. It heats the supply air when heat recovery alone is not sufficient to raise the supply air to the desired temperature. The desired temperature can be set by the user from the unit’s control panel.

The supply air temperature should be kept as low as possible without causing a feeling of draught. If you wish to increase the supply air temperature using the post-heating coil, it should not be set higher than the room temperature, as it is not practical to try to heat the dwelling with the ventilation unit.

If the supply air temperature is increased from 16°C to 22°C, the energy consumption of the post-heating function increases several times over. However, this energy use is offset by a corresponding reduction in the building’s heating energy demand.

Read more about the topic in our article.

What is the correct supply air temperature in winter?

The supply air temperature can be freely selected according to personal preference. The recommendation is that the temperature should be a couple of degrees lower than the room temperature. The higher the supply air temperature setpoint, the more electricity the post-heating function will consume.

During winter, heat recovery always warms the supply air using heat recovered from the exhaust air, regardless of the supply air temperature setting. A low supply air temperature may affect living comfort, but it has no effect on the operation of the ventilation unit or its defrosting automation.

The supply air temperature can be set separately for each operating mode (Home / Away / Boost / Custom).

How do I get the fireplace switch function to work?

Many Vallox ventilation units include a fireplace function, which is designed to assist with lighting a fireplace. In newer units, the same function can be achieved through a Custom setting. When the flue is still cold, the fireplace function creates temporary positive pressure inside the house. The fireplace function in ventilation units is not intended to provide combustion air for the fireplace.

When the fireplace function is activated, the positive pressure is maintained for approximately 15 minutes. In the fireplace profile settings of an MV unit, it is possible to select whether the extract airflow is reduced and/or the supply airflow is increased, and by how much. The duration of the fireplace function can be freely adjusted.

The fireplace function can also be implemented using a separate switch (momentary push button).

For more information, please refer to the user manual of your ventilation unit.

What does Heating season mean in the heating settings of the ventilation unit?

A new functionality, heating season, was added to the heating settings of the software version 2.0.24.

The addition was made to enable as efficient heat recovery as possible in the heating season and to make it possible to cool the home with outdoor air in spring and winter, without having to change the settings of the unit according to the season. At the same time, the electricity consumption of post-heating can be minimised safely. The outdoor temperature limit for the heating season can be set between 0°C and +19°C.

When the outdoor temperature sinks below the temperature set for the heating season, the heat recovery bypass automatics and partial bypass are not in use, that is, the heat recovery is always working at full capacity. In these circumstances, the supply air temperature may be higher than the temperature set for supply air. If the heat recovery cannot heat the supply air to the set temperature, the ventilation unit uses the post-heating resistor, when necessary. When the supply air temperature is set below 15 degrees Celsius, for instance, heat recovery will heat the supply air to a higher temperature for most parts of the year. Therefore, the post-heating resistor is only on during the coldest time of the year.

Please note that if the humidity of the indoor air is high, a supply air temperature that is too low may cause condensation in the supply air valves.

When the outdoor temperature rises above the outdoor temperature set for the heating season, the ventilation unit aims to heat the supply air to the set temperature by using full or partial heat recovery. The post-heating resistor will not turn on regardless of the supply air temperature setting.

In ventilation models without a partial bypass, heat recovery may heat the supply air to a considerably higher temperature than the supply air temperature setting.

The ventilation unit needs post- and additional heating resistors during defrosting cycles, so they must not be turned off, or stopping the supply fan must be chosen as the defrosting method.

How do I use the different fan speed settings of the ventilation unit?

In the ventilation unit, you can adjust the fan speed yourself for the Home and Away modes. You can choose to switch between the Home and Away modes according to your needs, the number of occupants, and the level of activity in the home.

You can also use the Automatic mode, which uses the fan speed setting of the Away mode and the temperature settings of the Home mode. Automatic mode is recommended only for ventilation units equipped with built-in humidity and carbon dioxide (CO₂) sensors.

You can learn more about your unit’s settings in the user manual.

How does the defrosting automation in Vallox ventilation units work?

All new MyVallox ventilation units feature SmartDefrost by Vallox®, a demand-based defrosting automation system that defrosts the heat recovery core only when necessary. This ensures a high annual heat recovery efficiency. The automation continuously measures temperatures around the heat recovery core and determines whether ice is beginning to accumulate in the core. When too much ice has formed, the core is defrosted. When core bypass is in operation, the ventilation unit bypasses the supply air side of the heat recovery core during the defrost cycle, and the heat from the extract air defrosts the core. Supply air continues to flow past the core, so the supply/exhaust air balance does not change.

During the defrost cycle, the supply air is heated by the unit’s post-heating element, and larger models also include an additional heating element, so cold outdoor air is not brought indoors. During the defrost cycle, the supply air temperature may fall below the setpoint value. Supply air continues to pass through the filters normally during defrost cycles. There may occasionally be ice in the heat recovery core and condensation water at the bottom of the unit. This is normal operation of the unit.

The ventilation unit requires the post-heating and additional heating elements during defrost cycles, so they must not be disabled unless supply fan stop has been selected as the defrosting method. As a result of stopping the supply air fan, negative pressure in the building may increase during the defrost cycle.

How can I influence the temperature of the air supplied by the ventilation unit?

The temperature of the air coming from the ventilation unit should be slightly lower than the room air temperature. This allows the air to circulate in the room and enables the warmer, used air to be removed from the space.

If you want to change the temperature control method, it can be set as follows:

Software version 2.0 or later:
Settings → Professional Settings → Control Settings → °C Control Mode

Earlier software versions:
Settings → Special Settings → Sensor Settings → °C Control Mode

How do you switch heat recovery bypass on in MyVallox units in summer?

Heat recovery bypass is automatic in MyVallox models. When outdoor air is warmer than the setpoint for supply air temperature, the unit switches bypass on. If outdoor air is warmer than the air going out from the dwelling, the unit uses cool recovery: it aims at cooling down the warm outdoor air with the coolness of extract air. The status of heat recovery and bypass is shown at the controller.

There is no separate summer/winter switch, but if you want to use the cooling function in summer, you have to set it: Special settings – Sensor settings – °C adjustment mode – Cooling. With this setting, ventilation is boosted automatically when supply air can be used to cool the dwelling.

What should I do if I have problems connecting the Wi-Fi module or opening the ventilation unit’s user interface in a browser?

You can try to resolve the issue using the steps below:

Network and connection settings

  1. Switching to mobile data. The phone redirects traffic to the mobile network because the Wi-Fi network does not have internet access. Solution: turn mobile data off completely, or disable Settings → Connections → Wi-Fi → ⋮ → Advanced settings → “Switch to mobile data” / “Adaptive Wi-Fi”.
  2. Manual proxy server. A proxy has been configured in the Wi-Fi settings. Solution: in the Wi-Fi network settings, set the proxy to “None”.
  3. Stuck network connection. Solution: “Forget network” and reconnect, or restart the phone.

Chrome browser

  1. “Always use secure connections” (HTTPS enforcement). Chrome attempts to use HTTPS, but the server does not respond to it. Solution: Chrome → ⋮ → Settings → Privacy and Security → turn the option off; enter the address in the format http://….
  2. Cached HTTPS redirect (HSTS). Solution: try an Incognito tab; if it works, clear your browsing data.
  3. Data Saver / Lite Mode. Older versions of Chrome may route traffic through Google’s proxy servers. Solution: disable the feature.
  4. Outdated Chrome version. Solution: update Chrome to the latest version (Chrome → ⋮ → Settings → About Chrome).
  5. Corrupted cache or cookies. Solution: clear the cache or test in Incognito mode.

Other applications

  1. VPN. An app-based or “always-on” VPN routes traffic away from the local network. Solution: disable the VPN.
  2. Antivirus / security application. Web protection, a built-in VPN, proxy, or firewall may block access to the local IP address. Solution: temporarily close the application; if that resolves the issue, disable only the specific feature causing the problem (usually “Web Protection” or “VPN”).

How can I tell if the ventilation unit is operating correctly?

Insufficient ventilation can be recognized by stale indoor air, moisture condensing on windows and surfaces, and poor removal of odours, especially in the kitchen or bathroom. These issues may be caused, for example, by incorrectly adjusted airflow rates, malfunctioning of the ventilation unit, or dirty filters in the unit.

Regular maintenance of the entire ventilation system is extremely important to ensure that the system operates optimally and efficiently. Maintenance responsibilities are divided somewhat differently depending on the type of housing.

What is the password for the KNX file?

The file does not have a password.

Some browsers download the file as a ZIP file.

Download the file using a different browser, or open it directly from your computer’s Downloads folder, and you will be able to save it in VD5 format.

What are the correct settings of Vallox MyVallox ventilation units in winter?

The settings of Vallox ventilation units are chosen at the factory to ensure their maximum energy-efficiency. Do not change any settings if you are not absolutely sure of what you are doing and how the change will affect the unit’s operation. If you change a setting, write down the original setting and the value you changed so that you can go back if necessary. The settings made at the factory ensure the correct and economical operation of the unit.

You can freely choose the supply air temperature according to your preferences. The recommended temperature is a couple of degrees below the temperature of the room air. The higher the default supply air setting, the more electricity post-heating consumes. In winter, heat recovery always heats the supply air with heat recovered from the extract air, regardless of the supply air temperature setting. A low supply air temperature can affect the comfort of living, but it has no effect on the operation of the ventilation unit or its defrosting automation. A specific supply air temperature can be set for each mode (At home/Away/Boost/Custom).

An example of setting the supply air temperature for the At home mode:

Using the MyVallox Control control panel (four buttons at the bottom): Set the unit to At home mode. Press (i) info -> pen icon -> use the arrow to go to Supply air temperature setting -> set the supply air temperature by using the – and + buttons. Press OK to confirm the value that you have set.

Using the MyVallox Touch control panel (touch screen): Menu -> Ventilation mode settings -> At home settings -> Supply air temperature setting -> pen icon -> set supply air temperature using the – and + buttons. Press OK to confirm the value that you have set.

Other important ventilation unit settings in winter include the following:

Menu -> Expert settings -> Defrost settings

Defrosting method: Bypass (Fan stop in the 90 and 121 models)

Supply air temperature setting. Supply air temperature during defrosting cycle (not selectable on the MyVallox Touch control panel)

Indoor air: %Rh 0 (not selectable on the MyVallox Touch control panel)

Outdoor air: °C 20. (Not selectable on the MyVallox Touch control panel)

Menu -> Expert settings -> Heating settings:

Post-heating method Electrical resistor (liquid radiator only 245 MV VKL). Must not be turned off, unless the defrosting method is changed to fan stop!

Additional heating method On/electrical resistor. Must not be turned off, unless the defrosting method is changed to fan stop!

Stopping the supply fan creates underpressure in the home during defrosting cycles.

Heating season (Factory setting 12°C) When the outdoor air temperature is higher than the set value, the heat recovery bypass automation is working and post-heating will not be switched on.

HR cell Aluminium (not selectable on the MyVallox Touch control panel)

Menu -> Expert settings -> Control settings:

°C adjustment method: Supply air (Extract air in Aito Kotilämpö)

Humidity: Automatic. The ventilation unit sets the correct humidity percentage according to the history data of the home. The ventilation unit cannot increase the indoor air humidity in the home.

Co2 limit. (Factory setting 800 ppm). The ventilation unit boosts the ventilation if the carbon dioxide level rises above the set value. This requires a carbon dioxide sensor to be connected to the unit.

Menu -> Expert settings -> 1/0 and bus settings -> External sensor settings

External sensor setting: None (THERE MUST NOT BE Air heating in any other units except Aito Kotilämpö!). If a separate duct radiator is connected to the ventilation unit, choose the correct setting. Duct radiator settings can be found under Is it possible to use a cooling or preheating radiator connected to ground heat in MV models?

Settings of the Custom (Fireplace) mode:

Please note! Long-term use of the Fireplace mode may cause a fault in the ventilation unit during freezing weather due to the low temperature of the supply air, which may cause the unit to turn off.

MyVallox Control panel (four buttons at the bottom):

Set the unit to Custom/Fireplace mode -> Press (i) Info -> pen icon.
Timer On
Duration 15 minutes
Supply air fan % Increase the percentage of the supply air fan by the required amount. Please note! A significant difference between the speeds of supply and extract air fans may cause a fault in the ventilation unit during freezing weather due to the low temperature of the supply air, which may cause the unit to turn off.
Extract air fan % At least as large as the fan percentage of the At Home mode
Supply air temperature setting 15°C

MyVallox Touch control panel (touch screen):

Menu -> Ventilation mode settings -> Custom (Fireplace) settings –> pen icon -> You can change the specific settings by moving the cursor on top of the setting and selecting the pen icon.
Timer On
Duration 15 minutes
Supply air fan % Increase the percentage of the supply air fan by the required amount. Please note! A significant difference between the speeds of supply and extract air fans may cause a fault in the ventilation unit during freezing weather due to the low temperature of the supply air, which may cause the unit to turn off.
Extract air fan % At least as large as the fan percentage of the At Home mode
Supply air temperature setting 15°C

Settings of cooker hood compensation:

Please note! Long-term use of the cooker hood compensation may cause a fault in the ventilation unit during freezing weather due to the low temperature of the supply air, which may cause the unit to turn off.

MyVallox Control panel (four buttons at the bottom):

Menu -> Professional settings -> 1/0 and bus settings -> Input settings -> Digital input 1 or 2 (select the one to which the cooker hood compensation is connected) -> Programmable input
Duration 00:01 (The mode is on as long as contact data is transmitted from the cooker hood.)
Supply air fan % Increase the percentage of the supply air fan by the required amount. Please note! A significant difference between the speeds of supply and extract air fans can cause a fault in the ventilation unit during freezing weather.
Extract air fan % At least as large as the fan percentage of the At Home mode
Supply air temperature setting 15°C

MyVallox Touch control panel (touch screen):

Menu -> Professional settings -> 1/0 and bus settings -> Input settings -> Digital input 1 or 2 (select the one to which the cooker hood compensation is connected) -> Pen icon -> Use the arrow to move to Programmable input and select OK. You can change the specific settings by moving the cursor on top of the setting and selecting the pen icon.
Duration 00:01 (The mode is on as long as contact data is transmitted from the cooker hood.)
Supply air fan % Increase the percentage of the supply air fan by the required amount. Please note! A significant difference between the speeds of supply and extract air fans may cause a fault in the ventilation unit during freezing weather due to the low temperature of the supply air, which may cause the unit to turn off.
Extract air fan % At least as large as the fan percentage of the At Home mode
Supply air temperature setting 15°C

Always check, in connection with maintenance or when it is suspected that the unit may not be operating normally, that the potential heat recovery cells are securely mounted. You can find their correct locations in your unit’s manual under Cleaning the heat recovery cell.

How much less energy does MyVallox 125 CFi consume than my old ventilation unit?

The heat recovery cell in old ventilation units is often significantly smaller than in modern, energy-efficient units. In addition, the fans of new devices often need less electricity than those of older models.

Below, you can find an indicative calculation of potential savings at a price of 20c/kWh for electricity. The calculation is based on the conditions in Central Finland. In Southern Finland, the required energy for heating is about 15% lower than the calculation, and in the north, about 20% higher. The location does not affect the energy consumption of the fans.

laskelma Vallox 125 MV

For more details, download the Excel file to help you assess energy consumption at the price of your electricity contract and your ventilation unit’s settings.

If a cooker hood is connected to the ventilation unit in the dwelling, which kind of cooker hood can be used to control an MV unit?

Method 1: Automatic cooker hood boosting with a self-programmed digital input

With the cooker hood boosting function, the fan speed of the ventilation unit increases when the flap of the cooker hood is opened.

Automatic cooker hood boosting can be implemented by bringing a control voltage of 24 V from the timer of the flap of the cooker hood, such as Vallox KTXA, to the digital input (1 or 2). The contacts of the timer of the cooker hood close when the flap is opened. In this case, Self-programmed input has to be chosen as the function for the digital input. In the settings for the Self-programmed input, switch the timer off, set the desired power for the supply and extract air fans as a percentage as well as the desired supply air temperature. These can be different from the setpoints of the other profiles. The supply/extract ratio can also be different from other profiles if you wish to compensate for the increase in the extract air flow caused by the opening of the flap of the cooker hood.

Method 2: Controlling fan speed at the cooker hood:

You can control the fan speed of an MyVallox unit (away/home/boost) with any cooker hood that gives a voltage signal (0-10 VDC).

Note! You cannot increase fan speed at the cooker hood higher than the Boost profile.

The MV unit is controlled in parallel with the MyValloxControl controller supplied with the unit. The latest command is always the one that stays in force.

In both cases, all the functions of the MyVallox unit are also controlled at the MyValloxControl controller.

MyVallox Unit Troubleshooting and Maintenance

Where can I find the nearest service provider and filter retailer?

You can find the nearest partners using our map service.

You can choose the appropriate category from the following options:

  • Authorized service provider
  • Installation company
  • HVAC designer
  • Distributor
  • Filter retailer
  • Importer

When purchasing filters, we recommend always choosing genuine Vallox filters from our online store.

 

Can I purchase Vallox spare parts or products?

Consumers cannot purchase spare parts directly from Vallox. Instead, they are advised to contact their nearest authorized service provider.

Vallox products can be purchased through wholesalers and directly from Vallox. However, it is also recommended that the purchase be handled by a professional who is responsible for the ventilation design of the home.

How often should the filters in a MyVallox ventilation unit be replaced?

The filters in a ventilation unit should be replaced at least twice a year. More frequent replacement is recommended if the building is located near a busy road, if there are pets in the household, or if any occupants suffer from allergies.

The condition of the filters should also be checked if the indoor air begins to feel stale. MyVallox units also provide a filter maintenance reminder.

When purchasing replacement filters, we recommend always choosing genuine Vallox filters from our online store.

Where can I find my unit’s model number?

The unit’s model number can be found on the rating plate, which is located inside the unit.

For ventilation units, the rating plate is located on the inner wall of the unit. For MyVallox ventilation units, the model number can also be found on the controller under the Unit Information menu.

Where can I find manuals for older Vallox ventilation units?

You can find manuals for discontinued Vallox ventilation units here.

How often does a ventilation unit need to be serviced?

Every six months, when replacing the filters, it is recommended to inspect the inside of the unit, check the condensate drain connection, and remove any dust that may have accumulated inside the unit.

Approximately every 5 to 10 years, it is advisable to have the ventilation ducts cleaned and the airflows rebalanced and adjusted by professionals.

How do I update my MyVallox ventilation unit?

A link to the update package and detailed instructions can be found on the dedicated software update page.

How do I restore factory settings on a MyVallox unit?

Instructions for restoring the factory settings can be found here: (techmanuals.info)

If you do not want to reset all of the unit’s settings, restore only the commissioning settings instead of the factory settings. This way, the adjustments made during the unit’s commissioning will remain in effect.

Restoring the factory settings means that the unit is returned to the state in which it was originally programmed at the factory. If the factory settings are restored, all commissioning-related settings (such as date and time settings, supply and extract airflow adjustments, and ventilation mode settings) must be configured again.

Note! Restoring the factory settings may disconnect the ventilation unit from the MyVallox Cloud service, and the unit may need to be registered with the service again.

How do I enable cooling in MyVallox ventilation units during the summer?

When the summer cooling function is enabled, the ventilation unit automatically increases the fan speed whenever outdoor air can be used to cool the dwelling.

If you want to enable the Summer Cooling function, configure it as follows:

Software version 2.0 or later:
Settings → Professional Settings → Control Settings → °C Control Mode → Cooling

Earlier software versions:
Settings → Special Settings → Sensor Settings → °C Control Mode → Cooling.

Why does the supply air fan stop intermittently in freezing weather?

In some ventilation units, frost protection for the heat recovery core is implemented by temporarily stopping the supply air fan. When there is a risk of the heat recovery core freezing, the unit briefly shuts down the supply air fan, allowing the heat from the extract air to defrost the core.

The extract air fan continues to run at all times, so the ventilation of the dwelling does not stop.

The frequency of fan stoppages depends on:

  • The outdoor air temperature
  • The ventilation speed setting
  • The temperature and humidity of the extract air

If the fan stops very frequently, the cause may be:

  • Insufficient insulation of the extract air ducts
  • Neglected maintenance
  • A technical fault in the system.

What does the “Low Supply Air Temperature” alarm mean?

The Low Supply Air Temperature alarm means that the supply air temperature of the ventilation unit has dropped below 5°C. This alarm is activated when the unit detects excessively cold supply air, which may be caused by severe freezing weather, a mechanical fault (such as a malfunctioning bypass damper, a failed heating element, or dirty filters), or abnormal airflow settings.

When a low supply air temperature is detected for the first time, the unit stops operating. After two minutes, the unit automatically restarts and checks the supply air temperature again. If the supply air is still too cold (below 5°C), the unit stops again and will not restart until the fault condition has been acknowledged and reset.

Software update 2.0.26 introduced changes to the alarm behavior: in Custom mode or when using a programmable input, the low supply air temperature alarm is not triggered, as these are considered special operating conditions intentionally configured by the user.

If the alarm occurs repeatedly, it is recommended to check:

  • The unit’s filters
  • Airflow settings
  • Any possible mechanical faults

In some cases, a software update may help resolve the issue, but mechanical faults must be repaired separately.

Why can a ventilation unit freeze?

A ventilation unit can freeze during winter because cold outdoor air and warm indoor air meet inside the unit. When this happens, moisture can condense and turn into ice on the extract air side of the heat recovery core.

Excessive icing can impair the operation of the ventilation unit. However, modern MyVallox ventilation units are equipped with automatic defrosting automation, which detects when moisture has frozen and automatically melts the ice that has accumulated inside the unit.

Why is water dripping from the ventilation unit?

The operation of a ventilation unit naturally produces water (condensate), which should drain from the unit into the sewer system through a condensate drain pipe and water trap, both of which are installed by professionals.

If the water is not draining properly into the sewer, you should check the following:

  • Whether the condensate drain pipe is blocked
  • Whether the water trap is functioning correctly
  • The condition of the filters

If the problem persists, it is recommended to contact the nearest HVAC service provider.

Why doesn’t the MyVallox controller display the indoor temperature, or why is it displaying it incorrectly?

Check the external sensor setting:

Menu → Professional Settings → I/O and Bus Settings → External Sensor Settings

External Sensor Setting: Not in Use (this MUST NOT be set to Air Heating in units other than Aito Kotilämpö systems).

If a separate duct coil has been connected to the ventilation unit, select the correct setting for it according to the duct coil’s instructions.

What does the “bussfault” alarm on the controller mean?

When the controller display shows “bussfault”, it usually indicates a Modbus communication problem. This can be caused by several factors, such as:

Incorrect Modbus address: Check that the ventilation unit’s Modbus address is configured correctly.

Transmission speed issues: Make sure that the Modbus baud rate is configured correctly in both the ventilation unit and the control system.

Parity errors: Verify that the Modbus parity setting is configured correctly.

Stop bits: Ensure that the Modbus stop bit setting is configured correctly.

These settings can be checked and configured using the MyVallox Control controller, MyVallox Touch controller, or the web user interface.

Ventilation Unit and Power Outage: What Should You Do?

A short and unexpected power outage does not require any special actions. During a power outage, it is a good idea to ventilate the home from time to time to allow fresh air to enter.

If the ventilation unit is equipped with a liquid-circulation coil, its freeze protection during power outages must be ensured, for example by using shut-off dampers in the outdoor air and exhaust air ducts. If the outdoor air duct of the ventilation unit is short, wind or the use of a fireplace may cause freezing air to flow into the unit even when the fans are not running.

Vallox ventilation units restart after a power outage using the same settings that were active before the interruption. The ventilation unit starts at the same speed that was in use prior to the power outage. An exception is the SE models, which restart at the so-called Basic Fan Speed after a power outage.

If the unit displays a fault indication after the power outage, restart the unit by unplugging it from the power socket for a moment and then plugging it back in. After this, the unit should restart and return to normal operation.

How do I know that heat recovery is on?

When heat recovery is on, the exhaust air is cooler than the extract air (indoor air). You can check these temperatures on the control panel display or in the MyVallox Cloud service. On cold winter days, the temperature of the exhaust air must be a few degrees higher than the temperature of the outdoor air. During defrosting cycles, the exhaust air temperature rises; this is normal.

Why does the ventilation unit bring 40-degree air into the house after a sauna even though it is cooler outside?

The ventilation unit flows outdoor air through the heat recovery cell and heats it up with the extract air. However, in the summer it is best to by-pass the heat recovery cell and bring in outdoor air without heating it. In older models, this can be achieved by adjusting the position of the summer/winter damper, or automatically in newer models. Different units have different settings that determine when the automatic heat by-pass is allowed. NOTE! If a professional has adjusted the settings during the unit deployment, they should be in order.

Ensure that the unit has clean filters so that the unit can take fresh outdoor air.

If the problem is not solved, contact the maintenance shop.

Does the fireplace switch stop the extract air fan altogether?

Not necessarily. You can choose in the fireplace profile settings of an MV unit if extract air flow is reduced and/or if supply air flow is increased, and you can also specify the amount of decrease or increase. You can freely choose the time period for the fireplace function. It is also possible to implement the fireplace function with a separate switch (push button).

The fireplace always needs to have a combustion air duct that comes directly from the outside to a location recommended by the fireplace manufacturer.

What does the supply air adjustment methods supply air, extract air, and cooling mean?

Operation of the supply air adjustment:

  • When the temperature of the air that comes through the heat recovery cell is lower than the set supply air temperature, the setting uses the heat recovery cell and the post-heating radiator to achieve the set temperature.
  • The heat recovery cell is bypassed if there is no need to heat the supply air.

Operation of the extract air adjustment:

  • If the extract air temperature is lower than the set supply air temperature, the setting increases the target value of the supply air setting (max. 10°C).
  • If the extract air temperature is higher than the set supply air temperature, the setting reduces the target value of the supply air setting (max. 10°C).
  • When the temperature of the air that comes through the heat recovery cell is lower than the supply air target value, the setting uses the heat recovery cell and the post-heating radiator to achieve the target value.
  • The heat recovery cell is bypassed if there is no need to heat the supply air.

Operation of the cooling adjustment:

  • If the extract air temperature is lower than the set supply air temperature, the setting increases the target value of the supply air setting (max. 10°C).
  • If the extract air temperature is higher than the set supply air temperature, the setting reduces the target value of the supply air setting (max. 10 °C) and boosts the fan speed based on the need up to the fan speed setting of the Boost mode. When the Boost mode is in use, the fan speed is increased based on the need up to the maximum speed.
  • When the temperature of the air that comes through the heat recovery cell is lower than the supply air target value, the setting uses the heat recovery cell and the post-heating radiator to achieve the target value.
  • The heat recovery cell is bypassed if there is no need to heat the supply air.

The permitted range of the supply air setting is +5…+25 °C. The recommended setting is +15 °C.
The post-heating radiator is only used in the heat recovery mode and during defrosting, and when the winter setting is higher than the outdoor temperature.

To change the temperature adjustment method, do as follows:

  • Software version 2.0 or newer: Settings – Expert settings – Control settings – °C adjustment method.
  • Older software versions: Settings – Expert settings – Sensor settings – °C adjustment method.

How can I change the fan speed set for Home mode?

A higher or lower number of occupants than expected may create the feeling that the ventilation is not suitable for your needs. The fan speed in Home, Away, or Boost mode can be adjusted if necessary. Instructions for doing so can be found in your ventilation unit’s settings. Changing the fan speed in these modes does not alter the supply/exhaust air balance of the ventilation system.

For example, setting the supply air fan speed in Home mode:

With the MyVallox Control controller (four buttons at the bottom):
Set the unit to Home mode. Press (i) Info → Pencil icon → Set fan speed using the and + buttons. Confirm the selected value with the Accept button.

With the MyVallox Touch controller (touchscreen):
Menu → Ventilation Mode Settings → Home Settings → Fan Speed → Pencil icon → Set fan speed using the and + buttons. Confirm the selected value with the Accept button.

Note! Insufficient ventilation may cause problems for occupants or damage to the building structure.

Note! The supply and extract fan speeds in the Professional Settings should not be changed after commissioning.

Why should the grille never be covered with an insect net?

The surface area of the net installed over the grille is much smaller than that of the unit’s filter, which means that it will become blocked much quicker than the coarse filter of the ventilation unit. This would lead to extra maintenance needs. One reason why the use of the net is explicitly prohibited is that the grille is difficult to access, for which reason it is not maintained regularly. We have seen places where no outdoor air has been blown into the apartment for years through the unit.

Another reason is that a net installed over the outdoor grille increases the flow resistance even when it is clean. It decreases the air flow and increases the noise level of the ventilation system.

Vallox ventilation units have a two-phased supply air filtering. The fine filter cassette filters the smallest of particles, whilst the coarse filter stops larger dust particles, preventing the fine filter from becoming blocked as quickly. Therefore, it is often advisable to hoover the coarse filters also between filter changes during the “dirtiest” season.

Frequently asked questions about Pureo air handling units

Purchasing a Pureo Air Handling Unit

What types of applications are Vallox Pureo air handling units suitable for?

Pureo air handling units are particularly well suited for commercial and institutional buildings, such as offices, schools, retail premises, and small to medium-sized public buildings, where efficient and energy-efficient ventilation is required.

Pureo units are also suitable for residential ventilation solutions when implemented as a centralized system or as a floor-by-floor ventilation solution.

How do I choose the right Pureo unit for my project?

The selection is based on the required airflow rate, the intended use of the space, energy-efficiency targets, and installation and space constraints. A suitable Pureo unit can be sized using the Pureo MySelecta selection software. Pureo air handling units are available in many different sizes, making them suitable for a wide range of spaces and applications.

What is SFP and what does a value of 1.8 mean?

SFP (Specific Fan Power) describes the electrical power consumption of the fans in relation to the airflow rate. The lower the SFP value, the more energy-efficient the ventilation system is.

A value of 1.8 is a typical energy-efficiency benchmark for ventilation systems in commercial and institutional buildings.

What do the letters SR, SX, and TX in the names of Pureo air handling units mean?

They refer to different models in the Vallox Pureo product range.

The letter T stands for Top and S stands for Side. This means that T-series units have top-mounted duct connections, while S-series units have side-mounted duct connections.

X indicates a plate heat exchanger, while R indicates a rotary heat exchanger (rotor).

TX series = top-mounted duct connections + plate heat exchanger
SX series = side-mounted duct connections + plate heat exchanger
SR series = side-mounted duct connections + rotary heat exchanger

What control options are available for Pureo air handling units?

A Pureo unit can be equipped with its own automation system, or it can be supplied as a terminal block unit, in which case control is carried out through the building automation system.

How can the operation of a Pureo system be automated?

Ventilation can be controlled based on factors such as CO₂ concentration, humidity, or occupancy, using sensors available as optional accessories.

What accessories are available for Pureo units?

Vallox Pureo units are available with a very wide range of accessories, including:

  • Cooling systems
  • Heating systems
  • Sound attenuation solutions
  • Automation and control systems
  • Indoor air quality control and measurement devices
  • Hydraulic accessories

In practice, this means that the unit can be fully customized to meet the specific requirements of the application (office, school, retail space, etc.).

You can explore all available accessories on the website: Vallox Pureo Accessories

How does a differential pressure transmitter work?

A differential pressure transmitter measures the pressure difference within the system and helps automatically regulate the airflow.

How does Pureo fault diagnostics work?

In Pureo units, fault diagnostics work by monitoring measurement data from sensors and components through the control system. The control system detects deviations from normal operation and displays alarms directly on the control panel or in the building automation system.

Is design support available from Vallox for commercial ventilation projects?

Yes. Technical support and sizing assistance are available for selecting a suitable Vallox solution. Professionals can contact Vallox sales representatives and explore the MySelecta Pureo sizing and selection software. It is a sizing and selection tool that can be used to choose the appropriate Pureo unit and determine operating parameters suitable for the project.

How is a Pureo air handling unit connected to a roof exhaust fan?

A Pureo unit is connected to a roof exhaust fan by integrating both into the same ventilation duct system and synchronizing their operation through the control system. This ensures that the exhaust airflow operates in balance with the Pureo unit.

Using a Pureo Air Handling Unit

What should be taken into account during the first months of operation?

Commissioning the unit and balancing the airflow rates is always the responsibility of a professional. After commissioning, the unit does not require any action from the user during the first few months.

However, it is a good idea to pay attention to whether the air feels fresh and whether the user notices anything unusual, for example with air pressure differences. If any concerns arise, a professional can be asked to reassess the situation.

Can the system of a Pureo unit be optimized afterwards?

Yes, the system can be upgraded later by adding accessories such as indoor air quality sensors. This allows the Pureo ventilation unit to be adapted as the needs of the commercial space change over time.

How is the Pureo system updated?

Software updates for Pureo units are carried out by a qualified professional during commissioning and maintenance procedures.

How is an air handling unit maintained?

The air handling unit should be maintained by a qualified professional in accordance with the maintenance plan specified in the user manual.

Typical maintenance tasks include:

  • Replacing filters
  • Cleaning the unit
  • Inspecting and verifying the operation of the system

Regular maintenance helps ensure reliable operation, good indoor air quality, and energy-efficient performance.

Can I adjust the settings of a Pureo unit myself as a user?

It is not recommended for users to adjust the settings of Pureo units themselves.

Where can I find the nearest Pureo service provider and spare parts or filter retailer?

You can find the nearest service provider and filter retailer on the map available on our website: Vallox Map

Where can I find the model number of my Pureo air handling unit?

You can find your Pureo unit’s model number on the rating plate attached to the unit’s casing, usually near the service door or on the inside of the unit.

Frequently asked questions about Vallox Fans

Purchasing and Using Vallox Fans

What types of fans are there?

The most common types of fans are roof fans, duct fans, wall-mounted fans, and axial fans. They differ from one another in terms of design, application, and installation method.

What do the letters in Helios by Vallox fan model names mean?

  1. Roof Fans

VDDT120 = Designed to withstand continuous airflow temperatures of up to 120°C

B VDD = Smoke extraction fan + ventilation

VDD Ex (ATEX) = For use in explosive atmospheres (hazardous areas)

VD = Traditional AC roof fan

2. Axial Fans

AMD = Axial fan with a three-phase motor

AMW = Single-speed axial fan

HFRW EC = Axial fan with an EC motor

HQW / HWW = Wall-mounted fan

3. Duct Fans

VARD = Three-phase duct fan

VARW = Single-phase duct fan

What types of applications are different fans suitable for?

Vallox offers solutions for continuous ventilation, smoke extraction, ATEX-classified hazardous areas, and T120-rated applications, where the fan is designed to withstand a continuous operating temperature of 120°C.

Does a building require one fan or multiple fans?

In small ventilation systems, a single fan may be sufficient. However, in larger buildings, multiple fans are often used to ensure even air distribution and operational reliability.

How do I choose the right fan?

The selection is based on the required airflow rate, pressure loss, noise requirements, and the installation environment. A suitable fan can be selected using the Exxeo Select or Helios Select selection software.

How much pressure loss can a fan handle?

The ability to handle pressure loss depends on the type of fan and its sizing. A correctly selected fan ensures sufficient airflow even in demanding duct systems with higher pressure losses.

Are the Vallox fans quiet?

The noise level of fans depends on the airflow rate, the type of fan, and the installation location. Noise levels can be influenced through proper sizing and by adding sound attenuators.

Detailed sound level data for specific models can be found in the product information on the website.

Purchasing and Using Vallox Exxeo Roof Fans

What do the letters DS and DPC mean in the Exxeo models?

These are model designations within the Vallox Exxeo roof fan range.

The DS model features an integrated dual-speed converter, making it suitable for replacing older two-speed AC roof fans.

The DPC model comes as standard with the capability for pressure control and airflow control, enabling energy-efficient and demand-controlled ventilation.

Which roof fan is suitable for renovation projects?

The Vallox Exxeo DS is a two-speed model designed for renovation applications.

The cable from the existing electrical distribution board (2 × three-phase supply + PE) is connected to the safety switch. This makes it possible to continue using the existing contactor control system and avoids the need to install a new cable.

What accessories can be installed on roof fans?

Vallox Exxeo roof fans can be equipped with a variety of accessories, including sensors for measuring outdoor temperature, duct air temperature, humidity, carbon dioxide (CO₂), and VOC compounds, as well as a time switch with enclosure for two-speed roof fan control and a potentiometer for 0-10 V control of the roof fan.

The basic Vallox Exxeo model can be equipped with an external temperature sensor, allowing the fan speed to be reduced when the outdoor temperature drops during winter, if necessary.

The DPC model can be fitted with two temperature sensors: one is used for outdoor air compensation, and the other is intended for air density correction based on duct air temperature.

Can a roof fan be connected to a Modbus network?

The Vallox Exxeo basic model and the DPC model are equipped with Modbus readiness directly in the fans, with the exception of the two smallest sizes.

Using the Modbus connection, it is also possible to control the two smallest exhaust fans through the control board.

Are roof fans available in different color options?

Yes, Vallox Exxeo roof fans can be factory-painted in the desired color, allowing the roof fan to blend more seamlessly with the building’s roof.

Where can I get help with designing a ventilation system that uses a roof fan?

Vallox Exxeo roof fans are available in the MagiCAD Cloud product database and can be used in AutoCAD and Revit software. In addition, the products are available in the Cadmatic HVAC software.

Vallox also provides its own ExxeoSelect selection and sizing software.

What should be taken into account when installing a roof fan?

The roof fan must be installed on the roof in such a way that maintenance procedures can be carried out safely. The unit is always supplied with an installation frame, which makes on-site installation of the roof fan easy.

All control equipment supplied with Exxeo roof fans is integrated and protected within its own enclosure behind the service hatch. A safety switch is always supplied pre-installed and pre-wired with the product.

How does a roof fan perform in different weather conditions?

Vallox Exxeo roof fans can be installed even in demanding climatic conditions. The zinc-magnesium coated steel sheet (corrosion category C4, painted C5) provides protection against corrosion and remains durable in all weather conditions.

Thanks to the unit’s design, rainwater is directed to the side of the unit, preventing water from flowing into the ductwork. In addition, the perforated roof cover protects the unit from leaves and other loose debris.

How is a roof fan maintained?

Vallox Exxeo roof fans are equipped with a tilting section, which allows the roof fan to be swung aside during maintenance.

Ensure that the power supply has been disconnected and that the impeller has come to a complete stop before touching the roof fan or fan components.

Any damaged parts must always be repaired or replaced using genuine spare parts.

Frequently asked questions about Cooker Hoods

Which cooker hood is suitable for replacing an old MUH cooker hood?

You can find the cooker hood compatibility table here.

Which cooker hood is suitable for mechanical ventilation?

In smaller apartments, the cooker hood’s extraction function can be connected to the ventilation unit, eliminating the need for a separate extractor hood or dedicated ducting for cooking fumes. The cooker hood can also be connected to a stove fan and house fan unit or a roof exhaust fan, in which case cooking fumes are extracted through a separate route.

The Vallox product range includes cooker hoods for both extraction methods. Vallox also offers cooker hoods designed for centralized duct systems in apartment buildings as well as for apartment-specific ventilation systems.

 

What is the difference between a cooker hood and a cooker extractor fan?

A cooker hood is equipped with a grease filter, lighting, and controls that can be used to control the ventilation system through the hood. A cooker extractor fan has its own motor and fan, which actively remove air.

Some cooker hoods can be connected to an in-line duct fan, which effectively turns the hood into a cooker extractor fan. Cooker hoods compatible with a duct fan include:

  • Vallox Delico PTD EC
  • Vallox Capto PTC EC
  • Vallox X-Line PTXP MC
  • Vallox X-Line PTXPA MC

A duct fan can also be installed in combination with other cooker hoods that support the control of EC fans.

Should I choose a cooker hood or a cooker extractor fan?

The choice between the two depends on the type of ventilation system installed in the building and what can be connected to it.

A cooker hood is the right choice if the building has a roof exhaust fan or if you are allowed to install the cooker hood in the same duct system as the ventilation unit.

A cooker extractor fan is the right choice if the building has a dedicated exhaust duct for cooking fumes and you are allowed to use a device with a separate fan motor.

Which cooker hood is suitable for my kitchen?

Choosing a cooker hood depends on the size and location of the cooktop, the mounting and control method of the hood, the desired features, ease of maintenance, budget, and appearance.

The width of the cooker hood is usually selected according to the size of the cooktop. The location of the cooktop affects whether a wall-mounted, cabinet-integrated, or island-mounted cooker hood is the most suitable option.

The required extraction airflow rate depends on how much and how often cooking is done in the home. The control method is determined by the type of fan used.

Cooker hoods are also available with a variety of features, such as a smoke limiter or a temperature monitor, which are worth considering before making a selection. When evaluating maintenance requirements, it is important to consider how easily the grease filter can be cleaned and how easy it is to keep the hood clean.

Vallox X-Line cooker hoods and residential ventilation units feature a fixed glass design and are intended for installation within kitchen cabinetry.

Vallox Delico is a Finnish-made cooker hood range suitable for a variety of kitchens. Its glass front panel is available in both white and black, and the hood integrates elegantly into the kitchen design.

Can a cooker hood be integrated into a kitchen cabinet?

The Vallox Delico range of cooker hoods can be easily integrated into a unified kitchen design. The hood can be incorporated into the kitchen cabinetry using a pull-out model.

With a hood installed in the underside of a cabinet, the front panel is pulled out during cooking, maximizing the extraction performance of the hood.

How high should a cooker hood be installed?

There must be a sufficient safety distance between the cooktop and the cooker hood. In most cases, the distance between the cooker hood and the cooking surface below should be at least 500-600 mm above an electric cooktop and 650-750 mm above a gas cooktop.

The installation must primarily comply with the requirements specified in the user manual of the appliance.

What do the letters in cooker hood model names mean?

The first part of the model name indicates the application (where the unit is used).

The last letters indicate the features (what the unit does).

KTX / KTD / KTC → For apartment building central exhaust systems (no built-in fan)

PTX / PTD / PTC → Controls a ventilation unit or roof fan (control hood)

TTX / TTC / LTC → Cooker extractor fan (with its own fan)

AC → For AC (alternating current) fans

EC → For EC (electronically commutated / DC) fans

AMotorized damper with timer operation

P → Extended control functionality / “forced control”

MC / SC → Special control or equipment version.

How does cooker hood extraction work?

The extraction airflow of a cooker hood draws air into the hood ductwork when the hood is in operation. The shape and size of the hood affect how effectively cooking fumes, steam, and odors are removed.

Cooker hood extraction can be implemented with a system that is separate from the building’s main ventilation system, using an in-line duct fan or a roof exhaust fan. Alternatively, the cooker hood can be connected to the building’s exhaust ventilation system through a ventilation unit.

How can a cooker hood be used to control a ventilation unit?

Method 1: Automatic cooker hood boost using a programmable digital input

With the cooker hood boost function, the ventilation unit’s fan speed increases when the cooker hood damper is opened.

Automatic cooker hood boost can be implemented by supplying a 24 V control voltage from the cooker hood damper timer (for example, from a Vallox KTXA cooker hood) to Digital Input 1 or 2. The timer contacts in the cooker hood close when the damper is opened.

The function of the digital input must be set to Programmable Input. In the Programmable Input settings:

  • Disable the timer.
  • Set the desired supply air fan and extract air fan power levels as percentages.
  • Set the desired supply air temperature.

These values can differ from the settings used in other operating profiles. The supply/extract air balance can also be configured differently from other operating profiles if compensation is needed for the increased extract airflow caused by opening the cooker hood damper.

Method 2: Fan speed control from the cooker hood

The fan speed of a MyVallox unit (Away / Home / Boost) can be controlled by any cooker hood that provides a 0-10 VDC control signal.

Note! The fan speed cannot be increased from the cooker hood beyond the fan speed defined in the Boost profile.

The MyVallox unit can be controlled simultaneously with the supplied MyVallox Control controller. The most recent command always takes precedence.

In both cases, all MyVallox unit functions can also be controlled from the MyVallox Control controller.

How is a cooker hood installed?

The installation of a cooker hood should always be carried out with the assistance of a professional. Ensure that the cooker hood is suitable in terms of dimensions and that the installation height is correct. Prepare the mounting either directly on the wall or underneath a kitchen cabinet.

Connect the cooker hood correctly to the ventilation system and complete the electrical connections. Test the operation of the hood, the airtightness of the ductwork, the exhaust airflow, and the functionality of any additional features.

How should a cooker hood be used correctly?

Always switch on the cooker hood or cooker extractor fan when cooking. If the hood has adjustable power settings, you can select the extraction level that most effectively removes cooking fumes and steam from the room air.

If the hood has an extendable steam collection section, it should be opened fully while cooking. This allows the hood to capture cooking fumes and steam over the widest possible area.

It is also recommended to keep the cooker hood or extractor fan running for a short period after cooking has finished. This helps ensure that all contaminants are removed from the indoor air and that the indoor environment remains fresh.

The post-operation period also ensures that any water vapor in the exhaust duct is completely removed.

How do I clean the grease filter?

Cleaning the grease filter helps ensure adequate exhaust airflow and should be carried out regularly, at least 1-2 times per month.

Warm water and a grease-removing detergent (such as dishwashing liquid) are suitable for cleaning the grease filter.

The grease filter must be allowed to dry completely before it is reinstalled.

How is a cooker hood maintained?

Grease stains resulting from cooking should be cleaned immediately, and the exterior surfaces of the cooker hood should be wiped regularly. A mild detergent solution is suitable for cleaning the exterior surfaces of the cooker hood.

In addition, the cooker hood filter should be cleaned at least 1-2 times per month.

If you notice any problems with the cooker hood’s exhaust airflow or control settings, please contact your nearest service provider.

Where can I find the model number of my cooker hood?

The model number of Vallox cooker hoods is located behind the grease filter, at the rear of the hood.
Frequently asked questions about duct installation

Which ventilation duct material is the right choice?

For ventilation ducts, you can choose between various steel duct solutions or plastic-based systems, such as the Vallox BlueSky ventilation system. The choice depends on factors such as the building structure and the available installation space for the ductwork.

BlueSky is an environmentally friendly choice, as it does not generate offcuts and waste pieces in the same way as other duct materials.

Is a plastic ventilation duct fire-safe?

The fire safety of the Vallox BlueSky system has been verified by a VTT research report.

When installing the BlueSky system inside P3-class buildings, the ducts must be enclosed with a material rated at least D-s2, d2, or covered with mineral wool insulation.

Which ventilation system is suitable for a confined installation space?

The Vallox BlueSky air distribution system is suitable even for confined installation spaces, such as low suspended ceilings. It can be installed easily inside partition walls, intermediate floors, suspended ceilings, enclosures, or concrete structures.

How to select a duct size?

In detached houses, the typical duct diameter is 160-200 mm. In the Vallox BlueSky system, however, air is carried in a large duct only as far as the distribution box. From there, an individual flexible 75 mm duct is routed to each air valve.

For airflow rates exceeding 8 dm³/s per valve, the use of two ducts in parallel is recommended. Using two smaller ducts makes the ductwork easier to install in confined spaces.

The use of one or two ducts also makes airflow measurement easier. Therefore, it is advisable to create the ventilation design specifically for the BlueSky system in order to take full advantage of its benefits.

Are silencers required in the ductwork?

Yes, silencers should generally be installed in all ventilation duct systems. In a BlueSky duct system, the silencers are installed between the ventilation unit and the distribution boxes.

Can the sound insulation of ventilation ductwork be improved afterwards?

The sound insulation of ventilation ductwork should be inspected regularly for possible damage, wear, and loose seals. Seals and insulation materials used for sound insulation may deteriorate or become damaged over time, reducing their effectiveness. Condensation water can also damage insulation materials if the drainage system is not functioning properly.

The repair and replacement of sound insulation is generally the responsibility of a professional.

Which duct system is suitable for a renovation project?

The Vallox BlueSky ventilation duct system is particularly well suited for renovation projects. Thanks to its design features, the ductwork can be installed even in confined spaces, and the ducts are flexible, making them quick to position and easy to measure in renovation applications.

Can the duct system be modified afterwards?

The Vallox BlueSky ventilation duct system is easy to modify after installation, as the ducting is flexible and can be easily disconnected from the distribution box.

How do I design and size a ventilation duct system?

Vallox offers a calculator for estimating the material requirements of a Vallox BlueSky ventilation system, allowing you to quickly and easily determine the quantity of system components needed for your project.

In addition, Vallox customer service and technical support are available on weekdays to assist with planning and sizing questions.

How are ventilation ducts insulated?

The Vallox BlueSky ventilation duct does not require insulation when installed in a heated space.

When installed in a cold space, the duct should be insulated with 20 mm closed-cell insulation.

How often should ventilation ducts be cleaned in a detached house?

There is no legal requirement mandating a specific duct cleaning interval for detached houses, but the general recommendation is to clean the ventilation ducts approximately every ten years.

The BlueSky duct system is easy to clean, as the ducts can be disconnected from the distribution boxes and cleaned completely in a single operation. In addition, the distribution boxes themselves can be opened, allowing them to be cleaned from the inside as well.

When is a duct radiator used?

A duct radiator is used in Vallox ventilation units when there is a need to provide additional heating or cooling of the supply air before it reaches the occupied spaces. The specific application depends on where the radiator is installed.

If the radiator is installed in the outdoor air duct, it can be used for:

  • Both preheating and cooling
  • Preheating only
  • Cooling only

If the duct radiator is installed in the supply air duct, it can be used for cooling only.

How is a duct radiator used?

A radiator connected to the collector circuit of a ground-source heat pump is not available as a built-in option in Vallox ventilation units, but an MLV radiator installed in the ductwork can be connected to them. Control of the pump and solenoid valve for the cooling and preheating circuit can be provided by the MyVallox unit’s automation system.

The 24 V control voltage can be used to control a contactor that starts the pump and opens the solenoid valve (External electrical connection, Duct radiator connection).

Remember to connect the wire between RM/I and +24 V.

How is a duct radiator controlled by a ventilation unit?

When an MV ventilation unit is used to control a duct radiator valve and actuator, it is recommended that the unit is running software version 2.0 or later. Control of a radiator installed in the supply air duct cannot be implemented with older software versions. If the unit is registered to the MyVallox Cloud service, it will always have the latest software version.

In addition to the radiator, a separate NTC temperature sensor (4109577) must be installed in the duct. The sensor is supplied with the Vallox MLV radiator and should be installed either before the radiator in the outdoor air duct or after the radiator in the supply air duct. The duct sensor temperature reading can be viewed at:

Menu → Service Menu → Unit Information → Page 5 “External Sensor”

The External Sensor Setting must be configured for either outdoor air duct radiator control or supply air duct radiator control, depending on the radiator installation location:

Settings → Professional Settings → I/O and Bus Settings → External Sensor Settings

The Relay Setting must be configured for external liquid radiator control:

Settings → Professional Settings → I/O and Bus Settings → Relay Settings

In the Duct Radiator Settings, select whether the radiator will be used for cooling, heating, or both.

The duct radiator can be configured to operate automatically or manually:

Automatic — In summer, the supply air temperature is maintained at the configured temperature setpoint. In winter, the duct radiator starts when the outdoor air temperature falls below the winter setting.

Manual — In summer, the duct radiator starts when the outdoor air temperature rises above the summer setting. In winter, the duct radiator starts when the outdoor air temperature falls below the winter setting.

To prevent condensation risk in the supply air duct, you can set the supply air limit control mode to either automatic or manual:

Automatic — The supply air limit is adjusted automatically based on the dew point of the extract air. If the supply air temperature falls too low, the duct radiator stops.

Manual — The supply air limit can be set manually. When the supply air temperature falls to the configured limit, the duct radiator stops.

See also: Setting the temperature control mode.

How does a wall air blow-out and intake unit work?

The Out/In Vario is designed for use as a residential exhaust air blow-out and outdoor air intake unit. Thanks to the patented design of the Vallox Out/In air blow-out and intake unit, the exhaust air discharge velocity can be adjusted in multiple stages, resulting in low pressure loss.

Due to its design, the unit has excellent water separation performance and is not prone to freezing. This significantly improves the operation of the ventilation system.

The unit is quick and easy to install and requires no maintenance.

The air blow-out and intake sections can be positioned separately, even on opposite sides of the building. This provides greater flexibility in building design and makes it easier to achieve the required minimum distances from factors that may reduce air quality (such as waste collection areas, adjacent balconies, etc.).

The unit’s handedness can be selected easily. The device is available in four different colours: white, brick red, black and grey.

In what types of houses is wall air blow-out suitable?

Wall air blow-out is a cost-effective solution for both apartment buildings and detached houses. By using wall air blow-out, significant cost savings can be achieved in the construction of the ventilation shaft.

Wall air blow-out is not suitable for houses located on small plots or for buildings that are situated very close to one another.

Does the Vallox Out/In unit have SERT R074 certification?

Yes, Vallox wall air blow-out units comply with the certification criteria of SERT R074: Exhaust Air Wall Blow-out Unit Certification.

This means that the Out/In Vario meets the equipment requirements for residential exhaust air wall blow-out and outdoor air intake applications.

usein kysytyt kysymykset Vallox Aito Kotilämpö ilmanlämmityskoneen käytöstä

How does an air heating unit work?

The Vallox Aito Kotilämpö unit includes a 6-row liquid-circulated heating radiator in its air heating section. This enables the dwelling to be heated efficiently while maintaining comfort without drafts, even with a relatively low recirculation airflow rate.

The output of the heating radiator is controlled from the same controller used for ventilation. However, the recirculation air fan has its own four-speed controller, with all speed levels being continuously pre-adjustable.

The ventilation section features a counterflow heat exchanger, and the annual heat recovery efficiency of the unit is approximately 77%.

Ventilation is controlled using a MyVallox controller or via the home network, building automation system, or cloud service.

The unit can be connected to all heating systems, including low-temperature ground-source heat pump systems.

The unit is equipped with built-in carbon dioxide (CO₂) and humidity sensors, which automatically boost ventilation as needed in response to changes in CO₂ levels and indoor humidity.

The MC defrosting automation maintains a high heat recovery efficiency even in severe freezing conditions and does not increase negative pressure in the building.

Which unit is suitable as a replacement for an old air heating unit?

Replacing an air heating system with a conventional ventilation system is often expensive, so simply replacing the unit itself is usually a good solution.

The Vallox Aito Kotilämpö is suitable as a replacement for, among others, the following older air heating units:

  • Valmet Kotilämpö
  • Thermovent
  • Himablock
  • ILA-15
  • Parma 10
  • Aeromaster
  • Oilon Oiva
  • Energiset

The dimensions, layout, and duct connection arrangements of the units may vary between different manufacturers and models, so it is advisable to be prepared for minor modification work during installation.

Are spare parts available for Valmet Kotilämpö?

Vallox and service centres authorised by Vallox continue to provide the most common spare parts for Valmet Kotilämpö. The price of the spare parts of Kotilämpö can be found in the Vallox spare parts price list.

How is a new air heating unit installed?

The installation of an air heating unit is always the responsibility of qualified professionals. During installation, it is important to consider the heating system in use, the condition and insulation of the ductwork, water and electrical connections, the operation of the distribution box, and condensate drainage.

How does heat recovery work in the Aito Kotilämpö?

The annual heat recovery efficiency of the Aito Kotilämpö is approximately 77%.

The Vallox Aito Kotilämpö uses the same MyVallox Control controller as Vallox ventilation units. The supply air temperature displayed by the controller represents the temperature of the air leaving the heat recovery (HRV) core.

During the heating season, the controller does not display the temperature of the air being supplied to the recirculation air duct. Instead, an external sensor measures the room air temperature, and the heating coil aims to deliver recirculated air at the requested temperature.

Vallox Aito Kotilämpö Air Heating Unit and Power Outage

The Vallox Aito Kotilämpö air heating unit restarts after a power outage using the same settings that were active before the interruption.

In the Vallox Aito Kotilämpö, the liquid-circulated radiator is located in the lower section of the unit, which means that the risk of freezing is low unless the power outage lasts for several days and the building temperature drops significantly.

By opening the Aito Kotilämpö access door, you can check the temperature in the lower part of the unit and, if necessary, allow warm room air to reach the radiator.

If the Aito Kotilämpö displays a fault indication after a power outage, contact your nearest service provider.

Why does Vallox Aito Kotilämpö report an error during the defrosting cycle?

If the control panel of Aito Kotilämpö reports an error, check the main settings first.

  • Defrosting method: Bypass, Indoor %Rh 0, and Outdoor air °C 20.
  • Heating settings: Heating method Electrical resistor (Must never be turned off!) Post-heating None.
  • Control settings: °C adjustment method Extract air and Humidity Automatic.
  • 1/0 and bus settings: External sensor Setting: Air heating. Relay settings: Air heating.

If the error persists, carry out a heater test as follows: When at least 5 minutes has passed since the error message disappeared, check the supply air temperature (°C) from the temperature display of the At home mode and write it down.  Next, test the additional heater. When the test has been on for a couple of minutes, you can exit the test. The supply air temperature should now be higher than previously in the temperature display of the At home mode. If this is not the case, the additional heating resistor or the relay that controls it is faulty. There is no need to carry out a post-heating test; in fact, the test cannot even be carried out, as the ventilation part of Aito Kotilämpö does not have a post-heating resistor.

Where can I find the nearest service provider and filter retailer?

Filter packages for the Vallox Aito Kotilämpö can be purchased from the Vallox online store.

The nearest authorized service provider can be found using our map service.

Where can I find the model number of my Aito Kotilämpö unit?

The model number of the Vallox Aito Kotilämpö is located inside the unit, on the inner wall.

Frequently asked questions about Vallox Filters

Where can I find the nearest authorized maintenance and filter retailer?

You can find the closest partners in our map service.

You can choose the right group from the following options: authorized maintenance, installation service, ventilation design, retailer, filter retailer or importer.

Where do I find the type code of my unit?

The type code is provided on the type plate inside the unit.

In ventilation units, the type plate can be found on the inner wall of the unit. In cooker hoods, the type plate can be found either at the bottom of the hood or behind the grease filter. In MyVallox ventilation units, the type code can also be found on MyVallox control, in the Unit information menu.

How can I identify an original Vallox filter?

Original Vallox filters are always supplied in a Vallox cardboard box. They feature Vallox branding and product information both on the packaging and on the label attached to the filter itself.

Genuine filters are manufactured using materials and dimensions specifically designed to ensure the optimal performance of Vallox ventilation units.

What is the filter classification of Vallox filters?

Older units use black G1 coarse filters and F5/F7 fine filters in accordance with the EN 779 standard.

The ISO 16890 standard replaced the EN 779 standard in 2018.

All newer Vallox and MyVallox ventilation units use ISO Coarse > 75% coarse filters and ISO ePM1 ≥ 50% fine filters in accordance with the ISO 16890 standard.

Chat